The name of created object | Name of the object created in the Pma objects tree. The maximum name length is 30 characters. This is a system name, so it must contain only alphanumeric and must not contain any diacritics (i.e. national dependent characters), empty string, spaces and the first character must not be a number.
Default: "CommIEC8705_104" |
---|---|
Network address | Network address of the remote device (e.g. of the PLC device), to which the communication will be connected.
The address can be entered as: - IPv4 full address (e.g. "192.168.0.15")
- IPv4 address of this computer (i.e. "127.0.0.1")
- IPv4 computer name (e.g. "server11")
- IPv4 name of this computer (i.e. "localhost")
- IPv6 full address (e.g. "2a02:c38:8136:800a:37a:ab66:6fc9:accd")
- IPv6 address of this computer (i.e. "::1")
Macro expression can be used for input (it is evaluated after the application is launched). After the preconfiguration is created, the "PmaComm > Setting the parameters of the Ethernet-client > Network address" configurator will be set to this value. |
ASDU common address size | The number of bytes (octets) for the ASDU Common address data: 1/2 bytes (PmaComm > Parameters > Protocol parameters)
1
2 (default) |
ASDU information object address size | The number of bytes (octets) for data object adress: 1/2/3 bytes (PmaComm > Parameters > Protocol parameters)
1
2
3 (default) |
Size of "cause of transmission" value | The number of bytes (octets) for the "cause of transmission". (PmaComm > Parameters > Protocol parameters)
1
2 (default) |