Promotic
WikipediaLinkedInYoutubeTwitterFacebook

SetUint16 - method of object PmBuffer

Description:
Writing integer 2 byte value with no sign.
Syntax:
Empty SetUint16(Long nOffset, Long nValue, [Long nEncoding])
Calling:
Value = PmBuffer.SetUint16(nOffset, nValue, nEncoding)
Parameters:
nOffset(Long) Defines the position of written value in the data block. The whole written item muyst be inside the data block, or the whole item is added to the end of the data block. The item is written either whole or not read at all.
The value -4 means that the internal automatic position is used (see AutoOffset). It points behind the last read or written value and increases continually. If the items are read/written one by one then it is not necessary to define the position, but it is handy to use this automated positioning.
The value -2 means that the whole item is added to the end of the data block. The size of the data bloc is then increased by the written item.
nValue(Long) Written value.
nEncoding[optional] (Long) Byte saving order in memory of a single value (Little-endian/Big-endian) in the data block. The Little-endian and Big-endian use different (reversed) order of value bytes storage in memory. This is not depending on the operating systerm but on the computer platform. In the PROMOTIC system (on x86 PC CPUs) the Little-endian is used. Big-endian is commonly used on ARM processors (often used in PLCs). Big-endian may be required for data exchange with another system (e.g. PLC).
0 (default) - Little-endian
1 - Big-endian
Note:
This method is also functional for Web panels.

History:
Pm9.00.04: Created
PROMOTIC 9.0.4 SCADA system documentation - MICROSYS, spol. s r.o.

Send page remarkContact responsible person