Analog alarms of variables

Setting of alarm of a analog variable by data extension:
 
- Select the "Data" tab in the "BoilerPlant/Boiler1/Data" object.
- Select the variable: "Temperature". Open the configuration window of this variable (by the Edit button or mouse doubleclick)
- Create a new data extension by the "Add" button and select: ExtAlarmAnalog.
- In the "Target object (PmaAlarmGroup)" configurator select (use the button with three dots) the previously created object of the PmaAlarmGroup type (the path to the object is "/BoilerPlant/Boiler1/Alarms").
- In the "Alarm template" configurator select (use the button with three dots) the automatically created alarm template named alarm0.
- In the "Source" configurator enter "Temperature of boiler no. 1".
- Enable the checking of all limits (1st+2nd low limit and 1st+2nd high limit).
- For all limits enter for example the following values:
2nd high limit = 95
1st high limit = 90
1st low limit = 10
2nd low limit = 5
 
Confirm all changes by pressing the button .
 

You have just configured the application to automatically check the value of the boiler temperature for exceeding the defined limits and once the limits are crossed the alarm is triggered.