Acknowledge - method of object PmAlarmItem

Description:
Alarm item acknowledgement.
Syntax:
Acknowledge([sUserNote], [tTimeAck], [sExtra])
Calling:
oAlItem.Acknowledge sUserNote, tTimeAck
Parameters:
sUserNote[optional] (String) The text note that is stored to the data together with the acknowledged alarm item (it is enabled on the "Storage" page).
tTimeAck[optional] (Date) The acknowledge time of the alarm. If not set, then the computer current time is used.
sExtra[optional] (String) Additional parameters parameters.

Entries are in KeyVal format, for example "ackerid:operator1;lang:en;".

"ackerid:xx;" - Identifier of user that acknowledged the alarm. This identifier is set into the AckerId property of the corresponding alarm and will also be written to disk into the AckerId column (if this column is enabled for writing to disc). If the parameter is not entered, then the identifier of user that acknowledged the alarm is used (local user or network user). For example"ackerid:operator1;".
"lang:xx;" - Specifies national language for Macro expression $.text. Language is determined with a text identifier, e.g. "en", "de", "ru" etc. - see Fully supported languages in the PROMOTIC system. If not set, then the present language of running application is used instead. This is relevant for multiple acknowledgement with filtration string switched on (e.g. $all;area:boiler1;), where it is possible to set the language for evaluation of localized fields. For example"lang:en;".
Note:
The acknowledgement succeeds only if the "Acknowledge" permission is fullfiled.

Calling the Acknowledge method over the acknowledged alarm has no effect. An unacknowledged alarm is acknowledged. The behaviour of the alarm during the acknowledgement is specified by the "Acknowledge type" configurator. The acknowledgement of the alarm is usually done interactively by the user from the viewer of an alarm group.

The method is synchronous, i.e. it is processed immediately by the alarm subsystem. Nevertheless writing the history to disk is asynchronous, it means that this method passes the request for writing to the history to the alarm subsystem, it is placed into the queue of requests and it is processed later by the alarm subsystem.

Example:
JavaScriptVBScriptSelect and copy to clipboard

var oAlItem = oAl.Item("Temperature");
oAlItem.Acknowledge("UserNote");