Promotic
WikipediaLinkedInYoutubeTwitterFacebook

Preconfiguration "eWON - Communication with cloud service Talk2M DataMailbox - Communication set with data and panel"

Configuration of communication with eWON.
 
This preconfiguration can be activated when creating a new object (e.g. by "New object" in the local object menu or by pressing the Insert key after selecting the object) and is included in the group: " / Communication / eWON PLC".

This preconfiguration can be used with the objects: PmFolder or PmRoot.

 
The preconfiguration creates main PmFolder containing three subfolders:
View - allows processing data in requested range from individual devices that are stored in cloud service Talk2M DataMailbox
Trend - allows reading and local storage of complete history of selected values from devices registered in the cloud service
Cfg - creates administration screen that can be used in order to create configuration file for trending selected values
 
In the GetAuthentication method of the main eWon folder there are all login entries requested for cloud service access.
 

View - PmFolder

The "PanelTest" test panel is used for displaying received data. Here it is possible to use the configurators in order to put together requested method and command parameter. The "PanelTrend" panel allows rendering graphic chart of data in defined time range.

The PmFolder object has methods RequestEwons, RequestEwon, RequestData and RequestSyncdata that are used to initiate the communication. Each of these methods call the Add method of the PmSequencer object together with corresponding parameters. It triggers the onStep event of the PmSequencer object where the HttpRequest object executes the communication with the service. The received data is then processed by methods ReplyEwons, ReplyEwon, ReplyData and ReplySyncdata that must be modified accordingly.

 

Cfg - PmFolder

Subobjects in this folder can be used to select values that will be read and saved locally into a trend database table. The CfgTrend panel is used for data selection and configuration. Once the configuration is saved, new file EwonCfgTrend.txt is created in the Cfg folder of the application. The content of such file is necessary for correct functionality of subobjects located in the Trend folder. These subobjects are responsible for saving selected values into trends.
 

Trend - PmFolder

Subobjects in this folder are responsible for communication and saving selected values into trends. Configuration file EwonCfgTrend.txt is necessary for their correct functionality. The file contains JSon data created by the CfgTrend panel. If increasing the number of trended values is needed, it can be done by opening the application in the development environment and copying the TrendVar1 object in the Trend folder.

Once the communication is launched for the first time the application starts reading all historical data (stored in the cloud) of variables defined in the configuration file. The order of variables is respected. The data is read and stored continuously from the oldes to the newest. The application reads batches of 200 records every 0.5 seconds (after the previous batch is processed). Once one variable is fully read then another follows. This process may take significant ammount of time based on the total ammount of data to be read. Once all the data is read and saved locally following communication is planned for the time defined in the DataCfg object in the Period variable. This value defines for how many seconds the system waits (after the previous communication ends) before the next reading of data from the cloud is initiated.

These configurators can be set before the preconfiguration is created:
The name of created objectName of the object created in the application object tree. This is a system name and must not contain diacritics, empty string, spaces and the first character must not be a number.

Default: "eWon"

Service account identifierassigned identification code of service account
Account nameUser account name
UserAccount login name
PasswordAccount login password
Demonstration of communication and data processingCreates View folder for demonstration and testing of communication and data processing
Save selected values into trendsCreates folders Trend and Cfg for configuration and trending of selected values
Number of trended valuesPlanned number of trended values
Data reading time periodTime period (in seconds) of repeated data reading
10 min
15 min
30 min
1 hour
2 hour
1 day
PROMOTIC 8.3.19 SCADA system documentation - MICROSYS, spol. s r.o.