Licence order

Innovation in control systems for medium-capacity wood chip boilers – Technical University of Košice

A system for the online monitoring and optimisation of the combustion process in wood chip boilers. The optimisation of the control algorithms is being carried out as part of a research project at the Technical University of Košice.

Introduction

The quality of wood chip combustion is closely linked to the amount of combustion air supplied to the combustion process. If a larger quantity of combustion air is supplied, energy losses occur (known as ‘chimney loss’). If less air than the optimum amount is supplied, incomplete combustion occurs, with some of the combustible substances being carried away in the flue gases. These consist mainly of carbon monoxide (CO) and hydrocarbons from the volatile components of wood. The combustible substances carried away in the flue gases not only result in losses in terms of fuel energy utilisation but are also air pollutants. Uncontrolled or improperly controlled combustion of wood chips can have a negative impact on the environment (particularly on local air quality), as is the case, for example, with uncontrolled coal combustion.

In order to ensure combustion that is as close to optimal as possible – i.e. achieving complete combustion with a minimum excess of air – new combustion process control algorithms have been implemented in the control systems of medium-capacity wood chip boilers.


Biomass combustion process control algorithms

Based on theoretical knowledge gained during the EU Structural Funds project ‘ Research and Development of Intelligent Systems for Biomass-Based Heat Production and Supply’, algorithms for controlling the biomass combustion process were designed, based on ensuring an optimal supply of fuel and oxygen to achieve the lowest possible CO emissions in the flue gas. The amount of oxygen supplied is determined by the so-called air excess coefficient, which is an indicator of the amount of excess combustion air relative to the stoichiometric amount. This coefficient has a significant influence on both combustion efficiency and CO emissions. The optimum operating range shown in Figure 1 is typically within the interval of 1.4 to 2 for the excess air coefficient during biomass combustion and depends on the moisture content and type of wood from which the wood chips are produced, the design of the combustion plant, and so on. The aim of the proposed combustion process control algorithms is to find, even when the properties of the wood chips change, a value for the excess air coefficient l at which CO emissions are minimised, thereby fulfilling the conditions for achieving maximum combustion efficiency. This requires accurate information on the actual oxygen concentration in the flue gas and trend data on the development of CO emissions in the flue gas (i.e. whether the CO concentration is falling or rising).

Innovation in control systems for medium-capacity wood chip boilers – Technical University of Košice

Figure 1: Typical relationship between CO concentration and efficiency as a function of the air excess coefficient l

Given the potential for the proposed algorithms to be used in practice, including in boilers of small and medium capacity, the criterion for selecting sensors to measure oxygen and CO concentrations in flue gases was that they should meet the required technical parameters whilst minimising procurement and operating costs

Implementation of an upgraded boiler control system

In order to implement new algorithms for controlling the combustion of wood chips, it was necessary to upgrade not only the software but also the technical components of the boiler control system. The following requirements were set for the control system for this upgrade:

  • a freely programmable control system to enable the implementation of new control algorithms,
  • the ability to update (download) application software online without the need to halt control processes and control loops,
  • a control system operator unit to enable the monitoring and modification of control parameters at the process level,
  • a sufficient number of digital and analogue inputs/outputs for sensing process states (DI), measuring process variables (AI) and controlling process actuators (RDO and AO).
  • communication interfaces for connection to the monitoring workstation via the internet (Ethernet), communication with heat meters (M-Bus), the lambda probe (RS232) and a GSM modem (RS232),
  • GSM monitoring for the operation of the process equipment.

Based on the above requirements, technical documentation was drawn up for the upgraded boiler control system to implement an automatic control and remote monitoring system for the combustion process, comprising the following basic components (Figure 2):

  • the AMiT/DIRAS process control system, based on the ADiS modular control system manufactured by AMiT, spol. s r.o., Prague,
  • a remote monitoring and control system based on the PROMOTIC SCADA product manufactured by MICROSYS, spol. s r.o., Ostrava,
  • the MoDir GSM monitoring system from Paufex Prešov, spol. s r.o., for operational monitoring of the technology by operators via SMS messages,
  • measurement of process variables for control and monitoring (boiler outlet water temperature, boiler return water temperature, flue gas temperature, furnace temperature, negative pressure in the combustion chamber, and concentrations of oxygen and carbon monoxide in the flue gas),
  • measurement of heat produced.

In addition to the sensors for the main process variables and the heat meter, the process control system is also connected to actuators for controlling the process equipment (fan frequency converters, servo drives, switching elements for fuel transport and feeding motors) and other control, interlocking and safety elements of the process

The upgraded control system was installed to control two different types (of varying capacities and from different manufacturers) of medium-capacity wood chip-fired boilers in real-world operational conditions, for the production of heat for heating and hot water supply in the residential and municipal sectors. New combustion process control algorithms have been implemented in the control systems, with the aim of ensuring that wood chip combustion is as close to optimal as possible.

A broadband planar two-element lambda probe with integrated heating is used to measure oxygen concentration; it utilises the boundary current principle to evaluate the oxygen content in the flue gas. In the range from l = 0.7 to, theoretically, l = ∞ (air containing 21% O₂), this probe provides a clear, continuous electrical signal at its output. The probe is supplied with a flange for fitting it into the flue (the pipe for exhaust gas discharge). The probe was used in conjunction with a transmitter that communicates with the control system via an RS232 interface.

Innovation in control systems for medium-capacity wood chip boilers – Technical University of Košice

A sensor whose resistance varies in response to the concentration of carbon monoxide is used to measure the concentration of carbon monoxide in flue gases. A conversion to a voltage signal was designed for the purpose of evaluating the sensor’s output. The sensor implemented in this way is used for an indicative measurement of the CO concentration in flue gases, given that information on the trend in carbon monoxide production (i.e. whether CO emissions are rising or falling) is important for the algorithm controlling the wood chip combustion process rather than an absolutely precise reading of its concentration in ppm or mg/m³. To mount this sensor in the flue (the flue gas exhaust pipe), a special bracket—protected as a utility model—was designed and manufactured. This allows the sensor to be positioned so as to ensure the best possible flow of flue gases to the sensor, whilst protecting it from damage caused by high temperatures in the flue gas pathways. This special bracket also facilitates the routine cleaning of the sensor to remove deposits forming in the flue gas path and allows for its easy replacement during servicing if necessary.

A type K thermocouple is used to measure the temperature in the combustion chamber. However, in some boilers, their design did not allow the measuring element of the thermocouple to be positioned so that the flame temperature could be measured directly. For this reason, the measured temperature is sometimes lower than the actual temperature, but this is not particularly significant for the control algorithm governing the wood chip combustion process. What is important is information on the temperature trend in the combustion chamber (i.e. whether the combustion temperature is rising or falling), rather than an absolutely precise reading of this temperature.

The operation of the installed control systems is monitored online, with records of the trends in individual process variables and the option to change control parameters and the implemented algorithms via the internet. The application developed within the SCADA system enables the continuous evaluation of heat production efficiency, as well as the display of time histories and interdependencies of measured variables that are important for assessing the quality of the combustion process. For visualisation purposes, graphical diagrams have been created showing basic information on the status of the process equipment. Figures 3 and 4 show examples of graphical diagrams for monitoring two heat sources with two different types of wood chip boilers installed, namely the boiler house of Dalkia Východné Slovensko, spol. s r.o. (Figure 3) and the boiler house of Bytenerg, spol. s r.o., in Medzilaborce (Figure 4).

Innovation in control systems for medium-capacity wood chip boilers – Technical University of Košice
Innovation in control systems for medium-capacity wood chip boilers – Technical University of Košice

Conclusion

The results achieved so far are in line with the theoretical assumptions and the stated objective of the innovation: to ensure wood chip combustion that is close to optimal (complete combustion with a minimum excess of air). The results of the validation of the proposed algorithms also indicate that, to achieve this objective, it is necessary to continuously optimise the quantities of fuel and air supplied to the combustion process based on the actual oxygen content and the indicative CO value in the flue gas. Further research and development work is currently focused on implementing predictive control algorithms using computational intelligence techniques to improve combustion efficiency, so that the combustion process takes place predominantly at lower oxygen supply levels within the optimal range, with the aim of achieving maximum combustion efficiency whilst complying with permitted CO emission limits.


Acknowledgements

This article was produced with financial support from the VEGA 1/0881/13 project ‘Research into algorithms and methods for the predictive control of biomass combustion processes’ and the ITMS 26220220030 project ‘Research and development of intelligent systems for the control of biomass-based heat production and supply’.




Authors:

Doc. Ing. Ján Piteľ, PhD.


Technical University of Košice

Faculty of Manufacturing Technologies, based in Prešov

Department of Mathematics, Informatics and Cybernetics

jan.pitel@tuke.sk




doc. Ing. Jaroslav Šeminský, PhD.


Technical University of Košice

Faculty of Mechanical Engineering

Department of Automation, Control and Communication Interfaces

jaroslav.seminsky@tuke.sk