Licence order

Emissions measurement monitoring - SPOLANA Neratovice a.s., Energy Plant

The measurement system monitors emissions measurement for 3 power boilers across 7 variables (SPM - solid particulate matter, SO2, CO, NOx, O2, temperature, flow rate). Emissions monitoring consists of 4 dispatch workstations (1 main, 3 clients). The main PC station is connected to an 8816 HW Datalogger, which serves as a data concentrator.

The measurement system monitors emissions for 3 power boilers across 7 variables (SPM - solid particulate matter, SO2, CO, NOx, O2, temperature, flow rate).

Emissions measurement monitoring consists of 4 dispatch workstations:

  • 1 main workstation: PC Server (Windows XP OS)
  • 3 client PC stations: PC control room (Windows XP/9x OS)

All PC stations are interconnected within the corporate Intranet. The main PC station is connected to an 8816 HW Datalogger, which serves as a data concentrator (supplied by ECM ECOMONITORING). The concentrator collects, evaluates, and archives measured data from the analyzers of all 3 boilers. The PROMOTIC communication task transfers the following from the datalogger:

  • One-minute averages of all measured variables
  • Half-hour averages processed from one-minute averages according to applicable legislation

Based on the retrieved data, the software provides the following functions:

  • Display of current and historical one-minute averages (table, graph)
  • Prediction of half-hour averages during the ongoing half-hour period
  • Comparison of predicted values with applicable emission limits
  • Visual and audible alarm in case of a threat of exceeding an emission limit
  • Display of half-hour averages (table, graph)
  • Processing of emission reports according to applicable legislation
  • Balance calculations (kg/day, month, year) according to applicable legislation
  • Export of one-minute averages to an MS Excel file

The entire system features a client-server architecture. Operators (dispatchers) can monitor measured data from any PC workstation. Applications are password-protected against unauthorized system entry (permission levels) and potential execution of other unauthorized programs. Data is archived in a dBase database; network clients are granted access to all archived (historical) data. The system is built modularly to allow easy future expansion with additional measurements.