PmModbusSl - Driver for communication by Modbus Slave protocol

Before using this driver in the PROMOTIC application it is highly recommended to read the chapter: Communicaton using the PROMOTIC drivers.
 
Basic properties of the driver:
- Using this driver is bound to purchase the license: PmModbusSl. With the freeware version PmFree, or when developing the application (with development environment for tersting purposes), this component is always functional.
- The communication is done via standard serial link (COM1, COM2 ...).
- The PROMOTIC application is always the SLAVE from this communication point of view (i.e. the other side initiates the data transfer). For MASTER communication see the PmModbusMr driver.
- The driver is incorporated into the PROMOTIC system by means of the PmComm object.

Driver supports to usage of PmCommMsg object. The PmCommData object cannot be used.

For easy integration of this driver into the application it is handy to use: Preconfigurations in group "Modbus protocol"

- The driver supports only the RTU mode for the SLAVE.
 
3 Modbus data types are supported:
- Bit (1Bit): stored in the PLC on 1 bit. In the PROMOTIC application it is represented by the Boolean data type.
- Word (2Byte Unsigned Integer): stored in the PLC on 16 bits (value from 0 to 65535). In the PROMOTIC application it is represented by the Long data type.
- Int (2Byte Signed Integer): stored in the PLC on 16 bits (value from -32767 to +32767). In the PROMOTIC application it is represented by the Integer data type.
 

The communication description by the PmCommMsg objects

The description of the protocol functions:

Each of eight messages can be started only once. This means that in the PROMOTIC system only eight messages can be defined together. If we need to read different memory fields, then the communication proceeds as follows:

- Master sends a query on the memory.
- The communication fills the Data-received page.
- The onDataReceive event fires.
- In the onDataReceive event the designer finds out from the Data-received page which address and the data amount are required from the Master and it fills the Data-sent page by them. If it doesn't have the data available, it sets the "Validity" item to false (invalid data), otherwise it sets this item to true (valid data) on the Data-sent page.
- The communication finds out if the "Validity" differs from false and it sends the appropriate data to the Master.

Note: If the "Validity" is set to true and the Data-received page isn't filled in onDataReceive event, the communication sends always the same data to the Master, regardless of the address that is requested by the Master.

Caution! If the "Validity" item is set to false, then the communication DOESN'T ANSWER the request !

 
The list and description of the communication messages:
01 - Read Coil Status (Read Output Bits): This message reads n output states (1-bit values)
02 - Read Input Status (Read Input Bits): This message reads n input states (1-bit values)
03 - Read Holding Registers (Read Output Registers): This message reads n output registers (16-bits values)
04 - Read Input Registers: This message reads n input registers (16-bits values)
05 - Force Single Coil (Write 1 Bit): This message writes into one state (1-bit values)
06 - Preset Single Register (Write 1 Register): This message writes into one register (16-bits values)
15 - Force Multiple Coils (Write n Bits): This message writes into n state (1-bit values)
16 - Preset Multiple Registers (Write n Registers): This message writes into n registers (16-bits values)