Promotic
WikipediaLinkedInYoutubeTwitterFacebook

Limit - page of object PmNumberLim

Description:
The condition for activating the alarm and invoking the onLimAction event of this object.
Configuration items:
Limit valueIf the value in the PmNumber parent object exceeds the specified limit, the alarm is activated.

This configurator sets the initial value of the property Limit.

Limit typeSelection of the limit type:
High limit - all values greater than the limit value will be alarmed
Low limit - all values less than the limit value will be alarmed
Fire 'onLimAction' eventDetermination when the onLimAction event has to be fired
Never - event will never be fired
Passing to the restricted area - event fires when the value before writing is inside the restricted area and after writing is already outside the restricted area
Passing from the restricted area - Event fires when the value before writing is outside the restricted area and after writing is already inside the restricted area.
Passing to/from the restricted area - Event fires after the conditions defined by the "Passing to the restricted area" and "Passing from the restricted area" are met.
On writing in the restricted area - Event fires when the writing value is inside the restricted area.
Alarm activation
Alarm groupName of the alarm group where the activated alarm is written. If the Don't activate alarm option is selected here, then this object won't use Alarm and Event system.
Alarm description (desc)Text (name) of the alarm that is also the identifier of the alarm.
When the alarm gets inactive acknowledged (green)When the limit is exceeded, it is the activation and when the value returns back, it is the inactivation of the alarm.
0 = by activation
1 = by inactivation
2 = by inactivation or by acknowledgement
3 = when inactivated and acknowledged
Sound notificationOption if the activated alarm has to be followed by the sound notification as well.
0 = no sound
1 = stop after aknowledgement or inactivation
2 = stop after aknowledgement and inactivation
3 = stop after acknowledgement
© MICROSYS, spol. s r. o.Tavičská 845/21 703 00 Ostrava-Vítkovice