AckerId - property of object PmAlarmEventItem

Description:
Identification of the user making alarm acknowledgement
Syntax:
AckerId As String
Calling:
oAlEvItem.AckerId
Note:
Property access for read and write. This property is filled in automatically by the Promotic system when the alarm is confirmed with the name of logged user that confirmed the alarm. If the alarm confirmation is implemented through the alarm viewer, then it corresponds to a local user. If the alarm confirmation is implemented through the network remote alarm viewer, then it corresponds to a network user. If the alarm confirmation is implemented through the Acknowledge script method, then it corresponds to a local user.

If the user specified text (other than system text) input into the property is needed, then the following system behaviour is defined: if any (non empty) value is written into the property at the moment of alarm confirmation, then it is not overwritten by the system value.

If the alarm item is active, then the value can be changed anytime by writing into this property. The modified value will be written automaticaly to the disk into the history when the alarm expires or when confirmed and also when the Promotic application is terminated.

See also: