Promotic
WikipediaLinkedInYoutubeTwitterFacebook

State viewer - page of item PmiAlarmEventView

Description:
The state viewer of an alarm/event group.
Configuration items:
Allow confirmationIf checked, the data of alarm/event items (of the PmAlarmEventItem objects) can be changed from the state viewer of the alarm/event group. For example, to acknowledge, add a note to the acknowledgement, etc.
Initial sorting
By time of emergence - newer items on top - The list of alarm/event items will be sorted by their times of emergence. Newer items will be listed above older items.
By time of emergence - newer items on bottom - The list of alarm/event items will be sorted by their times of emergence. Newer items will be listed below older items.
Hide inactive acknowledged (green) Allows to define whether to display inactive confirmed (green) alarms. Inactive confirmed (green) alarms can be divided into two types. New, non-initialized (non-existing so far) alarms and alarms that have been active in the past, but ceased existence.
0 = Show all - Inactive confirmed (green) alarms will all be displayed, i.e. the alarms of both types. Both new and expired alarms will be displayed.
1 = Hide all - Inactive confirmed (green) alarms will not be displayed. No new and no expired alarms will be displayed.
2 = Hide only new non-initialized - Inactive confirmed (green) alarms of the new non-initialized type (not activated so far) will not be displayed. Inactive confirmed (green) alarms that have been active in the past and are ceased now, will be dispayed. New alarms will not be displayed, ceased alarms will be displayed. See the configurator "PmAlarmEvent > Main > Change inactive confirmed (green) CEASED to NEW non-initialized alarms in [s] (-1=never)".
Time TypeFormat for displaying the data and the time.
0 = Time
1 = Date + Time
2 = Time + millisecond
3 = Date + Time + millisecond
Font for displayFont used for displaying the alarm/event item and its header.
Color modeDefines the color usage for selected alarm states and alarm markings indication. The alarm state is indicated by the selected color. The color is used for the text characters or the text background either for the first column or for the whole line. The selected alarm is distinguished by the color from other alarms (cursors). The current preset value is 0.
0 = State: whole row with color background. Selected: first column highlighted with black.
1 = State: whole row with color text. Selected: highlighted whole row.
2 = State: first column with color text. Selected: highlighted whole row.
3 = State: whole row with color text. Selected: first column highlighted with black.
4 = State: first column with color background. Selected: highlighted whole row.
Colors of alarm statesThe configurators allow to set colors for different alarm states. Caution: The colors are used for distinguishing differnt alarm states and therefore the modifications should be implemented wisely, because the default alarm color settings are used as references by the Promotic documentation, the designers and even the operators.
ColumnsThe configuration of individual columns. The columns can be added, removed and their order can be changed. Two entries are set for each column:
- Displayed name: Macro expression can be used for input ($.text ..) (it is evaluated while the application is launching).
- Displayed width (in pixels).
 

List of columns:

Id: >meaning:: preset state:
TimeOn Activation time displayed
TimeOff Inactivation time for alarm:displayed, for event:not used
TimeAck Acknowledge time for alarm:displayed, for event:not used
GlobalId Identifier of alarm/event item in group not displayed
Priority Priority of alarm/event item for alarm:displayed, for event:not displayed
Area Marking area of alarm/event item not displayed
Source Marking source of alarm/event item displayed
Desc Alarm/Event item description displayed
Comment Alarm/event item comment for alarm:displayed, for event:not used
UserNote Alarm/event item user note for alarm:not displayed, for event:not used
AckerId Identification of the user making alarm acknowledgement for alarm:not displayed, for event:not used
See also: