Promotic

PointsMaxVisibleCount - property of the PmgTrendViewer object

Description:
Maximum number of displayed points in viewer range.
Syntax:
Long PointsMaxVisibleCount
Note:
Property access for read and write. The default value of this property is defined in the "Maximum number of points rendered by a single trend progression" configurator of this object.
 
This property is also functional in Web panels.
 
The default value is 8000.
 
If, for example, the value of the property is set to 5000, then if the viewer has to display in the range of the time axis 7000 values, only 5000 oldest values are displayed. The value of this constant is also sent to the server that returns to the client no more values than there are set in this property.
The number of points sent from server to the client is also influenced by setting the "Maximum number of points returned in message by trend server (for one variable)" configurator.
If PointsMaxVisibleCount=-1, then the number of displayed points is limited by the maximum size of the buffer for the data and this is 60000.
Example:
JavaScriptVBScriptSelect and copy to clipboard

var oTView = pMe.Items("../TrendView");

var nMaxVis = oTView.PointsMaxVisibleCount;   // Reading from the property
oTView.PointsMaxVisibleCount = 10000;   // Writing into the property
PROMOTIC 9.0.27 SCADA system documentation MICROSYS, spol. s r.o.

Send page remarkContact responsible person
© MICROSYS, spol. s r.o.