Promotic
WikipediaLinkedInYoutubeTwitterFacebook

PointsMaxVisibleCount - property of object TrendsView

Description:

Maximum number of displayed points by the tvTrend object in the viewer range.

Default value of the property is 8000.

Syntax:
PointsMaxVisibleCount As Long
Calling:
oTView.PointsMaxVisibleCount = n
Note:
Property access for read and write. The preset value of this property is defined in the PointsMaxVisibleCount configurator of this object.

If, for example, the value of the property is set to 5000, then if the viewer has to display in its range of the time axis 7000 values, only 5000 oldest values are displayed.

The value of this constant is also sent to the server that returns to the client no more values than there are set in this property.

The number of points sent by the server to the client is also influenced by setting the configurator Maximum point count returned in message by trend server (for one variable).

If PointsMaxVisibleCount=-1, the number of displayed points is limited by the maximum size of the buffer for the data and this is 60000.