Preconfigurations PmModbusMr - AMiT modules DMM (Modbus RTU) - Communication set with data and panel

Communication by the Modbus RTU protocol with AMiT IO modules of the DMM series. See Communication with the IO modues by the AMiT company.
 
This preconfiguration can be activated when creating a new object (e.g. by "New object" in the local object menu or by pressing the Insert key after selecting the object) and is included in the group: " / Communications / Modbus protocol".

This preconfiguration can be used with the objects: PmFolder or PmRoot.

 
The preconfiguration creates the PmComm communication object and data for the corresponding number of analog and digital inputs and outputs. Also the panel with complex graphic items is created for displaying their status. This allows to define the required number for the specific connected device.
 
The preconfiguration is created for serial Modbus RTU communication. The modules use the RS485 bus for the communication. It is important to ensure that additional communication parameters are correctly configured (device address, port number, bit speed, parity, ...) The configuration procedure of the devices is described in the documentation provided by the manufacturer. The communication parameters of the PROMOTIC application are defined in Settings of the serial link parameters of the PmComm object and in Parameters of the PmCommData object.
 
- Preconfiguration creates an object of type PmFolder containing PmComm object with PmCommData subobject and following objects: PmPanel, PmData.
- The preconfiguration is created including the panel (PmPanel object) functionality as a WEB panel.
- The panel is used for communication testing and it is not essential for the functionality.
 
In the PmComm object named Comm the communication parameters (Serial port, ....) are set. The PmCommData object named Data includes a Parameters page where Special Parameters (See: PmModbusMr - Driver for communication by Modbus Master protocol) are defined. On the Data page, the items are imported by the data extensions of the items defined in the PmData object (See: ExtComm). Each Data corresponds to the selected device type by its structure and name.
 
Some types of the I/O modules (DMM-DI24) allow to use any of the binary inputs as counters. In this mode it is possible to read the walues but also write (reset the counter). Detailed specification and limitation is described in the documentation suppiled by the manufacturer.
 
This preconfiguration is not designed for modules of the DMM-FCx type. These devices allow only read/write to the specific addresses in the Modbus communication that has specific meaning.
These configurators can be set before the preconfiguration is created:
The name of created objectName of the object created in the application object tree. This is a system name and must not contain empty string, diacritics, spaces and the first character must not be a number.

Default: "CommAMiT_DMM"

Serial portSelection of the communication serial port.

After this preconfiguration is created, the configurator is se to: PmComm > Settings of the serial link parameters > Serial port.

Not set - The object is not connected to any port at the start of the application and the serial port can be selected dynamically by the algorithm (by the PmComm.OpenPort method).
Modem - The object is meant for the data transfer over the dialed phone line (over the PmModem object). The serial port is assigned by the PmModem.SetPmComm method or by the PmComm object configurator of the PmModem object.
COM1, COM2,..,COM66 - The specified serial port is opened at the start of the application. This port must be correctly configured and accessible in the OS Windows (no one can use it).

For serial link each PmComm object must have defined another communication port. For example, when one PmComm object communicates through COM1, then next PmComm object can communicate for example through COM2 (COM3,..) but it mustn't communicate through COM1.

Baud rateSelection of the baud rate (bps, bit per second).

This configurator sets the initial value of the property BaudRate.

After this preconfiguration is created, the configurator is se to: PmComm > Settings of the serial link parameters > Baud rate

110
300
600
1200
2400
4800
9600
14400
19200
38400
57600
115200
128000
256000
I/O module addressValid device address within the MODBUS network.

After this preconfiguration is created, the configurator is se to: PmCommData > Parameters > Special Parameters > Default PLC address

Communication refresh rate [ms]The time period in milliseconds to be used for reading the data by the PROMOTIC application. After this preconfiguration is created, the configurator is se to: PmCommData > Parameters > Communication refresh rate [ms]
The number of analog inputsPossible to enter the number according to the device type
The number of digital inputsPossible to enter the number according to the device type
The number of digital inputs used as countersPossible to enter the number according to the device type
The number of digital outputsPossible to enter the number according to the device type