Preconfigurations PmIEC8705 - Ethernet 104 - Communication set with data and panel

Configuration of the PmIEC8705 communication driver with test panel.
This preconfiguration can be activated when creating a new object (e.g. by "New object" in the local object menu or by pressing the Insert key after selecting the object) and is included in the group: " / Communications / IEC8705 protocol".

This preconfiguration can be used with the objects: PmFolder or PmRoot.

- Preconfiguration creates an object of type PmFolder containing PmPanel objects and PmComm object with PmCommMsg and PmCommData subobjects.
- The preconfiguration is created not including the panel functionality as a WEB panel.
- The panel is used for communication testing and it is not essential for the functionality.
These configurators can be set before the preconfiguration is created:
The name of created objectName of the object created in the application object tree. This is a system name and must not contain empty string, diacritics, spaces and the first character must not be a number.

Default: "CommIEC8705_104"

Network addressNetwork address to which the communication will be connected. The address can be entered by both IP address (e.g. or by name (e.g. server11).

Macro expression can be used for input (it is evaluated while the application is launching).

After this preconfiguration is created, the configurator is se to: PmComm > Settings of the Ethernet parameters > Network address
ASDU common address sizeThe byte count (octets) for the ASDU Common address data: 1/2 Bytes (PmComm > Parameters > Protocol parameters)
2 (default)
ASDU information object address sizeThe byte count (octets) for data object adress: 1/2/3 Bytes (PmComm > Parameters > Protocol parameters)
3 (default)
Size of "cause of transmission" valueThe byte count (octets) for the "cause of transmission": 1/2 Bytes (PmComm > Parameters > Protocol parameters)
2 (default)